Overview ¶
Package dnp3 decodes DNP3 (Distributed Network Protocol 3) frames per IEEE 1815-2012. DNP3 is the dominant utility-SCADA protocol in North American power-grid, water, and oil-and-gas telemetry — the field-bus protocol an attacker tapping into a substation, pumping station, or pipeline RTU is most likely to see on the wire.
Operationally, DNP3 carries:
- **Master ↔ outstation polls** ("read class 1 events" / "operate breaker") across leased lines, IP/TCP (port 20000) or IP/UDP between SCADA control centres and field RTUs.
- **Unsolicited responses** from outstations reporting state changes (breaker open, transformer over-temperature) without waiting for a poll — a defining DNP3 capability.
- **Time synchronisation + freeze-at-time** for substation event sequencing (used alongside PTP in IEC 61850 deployments where DNP3 still owns the SCADA application layer).
- **File transfer** for outstation firmware updates and configuration drops (function codes 0x19–0x1E).
- **Secure Authentication** (IEEE 1815-2012 §7, function codes 0x20 / 0x21 / 0x83) — HMAC-SHA256 based message authentication retrofitted onto the protocol.
Wrap-vs-native judgement
Native. IEEE 1815-2012 is fully public; DNP3 has a tight 10-byte data-link header followed by a transport byte, a 2- or 4-byte application header, and a series of objects whose per-group/variation prefixing rules are documented but deferred (object decoding is dataset-specific). No crypto at the parse layer — Secure Authentication payloads are surfaced as hex.
What this package covers
**Data-link layer header** (IEEE 1815-2012 §10.3, 10 bytes; little-endian where multi-byte):
bytes 0-1: Start = 0x05 0x64 (sync).
byte 2: Length (count of bytes that follow the Length field excluding CRCs — so Control + Dest + Src + user data; range 5-255).
byte 3: **Control field** — bit 7 DIR (1 = master-to- outstation direction), bit 6 PRM (1 = primary message, 0 = secondary), bit 5 FCB (frame count bit; toggles on retries) or DFC (data flow control; ack- buffer-overflow indicator) for secondary, bit 4 FCV (frame count valid) or RES (reserved), bits 3-0 primary or secondary function code. The decoder surfaces all five fields and the 4-bit code name.
bytes 4-5: Destination address (uint16 LE).
bytes 6-7: Source address (uint16 LE).
bytes 8-9: Header CRC (uint16 LE; CRC-16 with polynomial 0x3D65 over the 8-byte header; surfaced as hex but not re-computed).
**5-entry primary function code name table** (IEEE 1815-2012 §10.3.3): 0 RESET_LINK_STATES / 1 TEST_LINK_STATES / 2 CONFIRMED_USER_DATA / 3 UNCONFIRMED_USER_DATA / 9 REQUEST_LINK_STATUS.
**4-entry secondary function code name table**: 0 ACK / 1 NACK / 11 LINK_STATUS / 14 NOT_FUNCTIONING.
**User-data block walker** (IEEE 1815-2012 §10.3.2.5): user data following the 10-byte header is split into blocks of 16 bytes each (last block may be shorter) followed by a 2-byte block CRC. The decoder strips the per-block CRCs and reconstructs the user-data byte stream for higher- layer parsing.
**Transport function byte** (IEEE 1815-2012 §8.2, 1 byte at the head of the reconstructed user-data stream): bit 7 FIN (final segment of an application fragment chain), bit 6 FIR (first segment), bits 5-0 sequence number.
**Application header** (IEEE 1815-2012 §4.2.2): byte 0 = Application Control (bit 7 FIR + bit 6 FIN + bit 5 CON (confirm requested) + bit 4 UNS (unsolicited) + bits 3-0 SEQ); byte 1 = Function Code; for responses (function codes 0x81 / 0x82 / 0x83) bytes 2-3 = IIN (Internal Indication, 16-bit LE).
**20-entry application function code name table** (selected high-runners from IEEE 1815-2012 §6.2): 0x00 CONFIRM / 0x01 READ / 0x02 WRITE / 0x03 SELECT / 0x04 OPERATE / 0x05 DIRECT_OPERATE / 0x06 DIRECT_OPERATE_NR / 0x07 IMMED_FREEZE / 0x08 IMMED_FREEZE_NR / 0x09 FREEZE_CLEAR / 0x0A FREEZE_CLEAR_NR / 0x0B FREEZE_AT_TIME / 0x0D COLD_RESTART / 0x0E WARM_RESTART / 0x14 ENABLE_UNSOLICITED / 0x15 DISABLE_UNSOLICITED / 0x17 DELAY_MEASURE / 0x18 RECORD_CURRENT_TIME / 0x20 AUTHENTICATE_REQ / 0x81 RESPONSE / 0x82 UNSOLICITED_RESPONSE / 0x83 AUTHENTICATE_RESP.
**16-entry IIN-bit name set** (IEEE 1815-2012 §4.2.4; both bytes): IIN1 = BROADCAST / CLASS_1_EVENTS / CLASS_2_EVENTS / CLASS_3_EVENTS / NEED_TIME / LOCAL_CONTROL / DEVICE_TROUBLE / DEVICE_RESTART; IIN2 = NO_FUNC_CODE_SUPPORT / OBJECT_UNKNOWN / PARAMETER_ERROR / EVENT_BUFFER_OVERFLOW / ALREADY_EXECUTING / CONFIG_CORRUPT / reserved / reserved. The decoded comma- separated set is surfaced alongside the raw 16-bit hex.
What this package does NOT cover (deliberately out of scope)
- **Transport framing** — IP/TCP port 20000 (default), UDP/ 20000, or serial RS-232/422/485 lines. Feed DNP3 bytes after the transport-header strip.
- **CRC verification** — the data-link header CRC and the per-16-byte-block CRCs are surfaced as hex but not re- computed against IEEE 1815-2012 §E (CRC-16-DNP, polynomial 0x3D65, init 0x0000, reflected, xorout 0xFFFF).
- **Object header walker** — past the application header DNP3 carries a stream of Object headers (Group + Variation
- Qualifier + Range + count + objects). The per-group decoder set is large (Binary Inputs, Counters, Analog Inputs / Outputs, Time-and-Date, File-Control, Authentication ...) and dataset-specific; remaining bytes are surfaced as `object_data_hex` for future per-group walkers.
- **Secure Authentication payload** — function codes 0x20 / 0x21 / 0x83 carry HMAC-SHA256-protected Authentication blocks per IEEE 1815-2012 §7; payload surfaced as hex.
- **Multi-fragment reassembly** — the transport-byte FIN/FIR flags and sequence number identify multi-segment application fragments; the decoder surfaces the flags but does not reassemble across multiple input frames.
- **State-machine reasoning** — primary/secondary frame-count- bit logic, ENABLE_UNSOLICITED timer state, freeze-counter semantics; higher-level analysis.
Index ¶
Constants ¶
This section is empty.
Variables ¶
This section is empty.
Functions ¶
This section is empty.
Types ¶
type Result ¶
type Result struct {
TotalBytes int `json:"total_bytes"`
// Data-link header
StartHex string `json:"start_hex"`
Length int `json:"length"`
ControlHex string `json:"control_hex"`
DIR bool `json:"dir_master_to_outstation"`
PRM bool `json:"prm_primary_message"`
FCBOrDFC bool `json:"fcb_or_dfc"`
FCVOrRES bool `json:"fcv_or_res"`
LinkFunctionCode int `json:"link_function_code"`
LinkFunctionName string `json:"link_function_name"`
Destination int `json:"destination"`
Source int `json:"source"`
HeaderCRCHex string `json:"header_crc_hex"`
// Transport layer
TransportFIN bool `json:"transport_fin,omitempty"`
TransportFIR bool `json:"transport_fir,omitempty"`
TransportSeq int `json:"transport_seq,omitempty"`
// Application layer
AppControlHex string `json:"app_control_hex,omitempty"`
AppFIR bool `json:"app_fir,omitempty"`
AppFIN bool `json:"app_fin,omitempty"`
AppCON bool `json:"app_con_confirm_requested,omitempty"`
AppUNS bool `json:"app_uns_unsolicited,omitempty"`
AppSeq int `json:"app_seq,omitempty"`
AppFunctionCode int `json:"app_function_code,omitempty"`
AppFunctionName string `json:"app_function_name,omitempty"`
// Response-only
IINHex string `json:"iin_hex,omitempty"`
IINBitsDecoded string `json:"iin_bits_decoded,omitempty"`
// Remaining object data
ObjectDataHex string `json:"object_data_hex,omitempty"`
// Reconstructed user-data stream (post-CRC strip, no
// transport/application bytes consumed) for callers who want
// to feed it through their own walker.
UserDataHex string `json:"user_data_hex,omitempty"`
}
Result is the structured decode of a DNP3 frame.